Nitrogen Solenoid Actuator
Electrical actuation of a nitrogen cylinder is accomplished by a nitrogen solenoid actuator P/N 980027 interfaced thru an FM approved releasing panel. A local manual override valve actuator must be installed on top of the actuator to provide and emergency manual override in case or failure to the automatic operation. The solenoid actuator has nominal operating voltage of 24VDC @ 0.5amps ± 10%.Electrical classification—NEMA 4x (IP65)
FM Approved

NOTE: Before assembly or after system activation check to make sure that the tripping device (pin) has been reset. See Section 6 (Commissioning and Servicing) of the design, Installation & Service Manual for resetting instructions. Failure to assure the activating pin is in the non-activated position could cause system activation up installing the solenoid actuator.